INDustrial UPS

Industrial UPS: Construction

Cabinet

Robust, self-contained steel frame, meeting the specified IP-degree, allowance for air filters

Material

Corrosion-proof components and connections

Layout

Good accessibility and operability, clear and permanent component identification

Wiring

Non-halogenated wiring insulation with a high temperature degree

Industrial UPS: Design criteria

Accessibility

Quick and safe accessibility in case of failures or maintenance activities, Low MTTR due to easy front access

Replaceability

Simple replacement of modules/ assemblies (almost) without

Fans

N+1 or 100% redundant fans in case natural

Industrial UPS: Construction

Redundancy

Cooling is not adequate

Replacement

Safe replacement without disturbing the load

Lifetime

Extended replacement intervals

S3000: Unique feature battery mgmt. with integrated battery discharger

Constant current battery discharge test by means of sinusoidal mains back-feed

Battery monitoring with programmed discharge data

Periodic automated battery availability check

Real time battery capacity and back-up time display

Three voltage levels / two current limitation steps

Temperature compensation

SMT – Statron Modular Technology

24, 48, 110, 220 VDC modules

1kW to 3kW modules (typ.3kW)

Hot swappable

uP controlled

Very low input THDi < 4%

Galvanic isolated output

SMT: Main features and advantages

For NiCd and lead acid batteries

Automatic and manual boost charge with interlocking

2x100% and n+1 solutions

Modern touch display for status, metering and alarms

Modbus / TCP/IP Interface, RS485 / SNMP

Event history

Total system solutions